RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 8 – WATER HEATER MANAGEMENT

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 123 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

WHM MENU

See section 8-6 for a range of choices and the default values.

ITEM

MENU LEVEL &

OPTION

DESCRIPTION

14

WHM Max Addr

Set the maximum address of the heaters to be controlled by the master. The
WHM Min Addr and WHM Max Addr must differ by no more than 7.

15 SSD

Address

The Modbus Address of the SSD Device (Protonode). Set this address to
247 if the WHM system is being monitored by a Protonode with Slave –Slave
(SSD) programming. Set to zero (0) if no Protonode is installed.

16

SSD Temp Format

SSD temp values can be accessed in Degrees or Points

17

1 Valve Status 8

Displays the valve status of all the units.

0= valve closed
1= valve open
2= valve stuck closed
3= valve stuck open

18

1 Comm Errors 8

Display Comm Errors of all the units.

19

&

20

WHM On Delay

WHM off Delay

Specifies the WHM On and Off time delays associated with the Next ON VP
and Next OFF VP menu options. Therefore, if the Next ON VP or Next OFF
VP is at its preset Valve Position (%) for the specified Delay period, another
heater will be turned ON or OFF. This is done to prevent cycling units on and
off during short changes in load.

21

Over WHM Under

This value is a Factory debugging tool.

22

WHM Min Units

Specifies the Minimum number of units required to be “on” or “active”.

23

WHM Warmup Time

Specifies the time a valve will remain closed when turning on a unit in order
to assure that we do not release cold water into the building. When turning
on a unit, the valve will open when either the Warmup Timer times out or the
FeedForward Temperature reaches Setpoint.

24

WHM On Timeout

Specifies the time the WHM Master waits for a slave unit to turn On.

25

WHM Valve State

Displays the status of the WHM Sequencing Valve.
(1 = ON, 0 = OFF)

26 Valve

Override

Valve Override allows the user to manually control an Isolation Valve as
follows:
Off– Valve Override is disabled and WHM will automatically control the
Isolation Valve.
Open – Valve Override is enabled and the Isolation Valve is Opened.
Note! The valve will remain opened as long as the Valve Override feature is
set to Open. Care must be taken to insure that this mode is turned Off during
normal WHM operation.
Closed – Valve

27 Valve

Feedback

Enable or disable the Valve feedback feature

28

Valve Fdbk timer

The time allotted the Valve to Open or Close once a command has been
issued before invoking a fault.

29 ValveFdbk

Status

Displays a Valve status of the unit:

0= valve closed
1= valve open
2= valve stuck closed
3= valve stuck open