CHAPTER 4 – INITIAL START-UP

Page 66 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

4.5 OVER-TEMPERATURE LIMIT SWITCHES

The unit contains both automatic and manual reset over-temperature limit switches. These
switches are mounted as shown in Figure 4-5.

The manual reset switch is not adjustable and is permanently fixed at 190°F. This switch will shut
down and lock out the heater if the water temperature exceeds 190°F. Following an over-
temperature condition, it must be manually reset by pressing the RESET button before the heater
can be restarted. The automatic reset over-temperature switch is adjustable and allows the unit to
restart, once the temperature drops below its temperature setting. Set the automatic over-
temperature switch to the desired setting.

Figure 4-5: Over Temperature Limit Switch Location and Features

AUTOMATIC RESET (ADJUSTABLE)

TEMPERATURE OVER- LIMIT SWITCH

MANUAL RESET (NON-ADJUSTABLE)

OVER-TEMPERATURE LIMIT SWITCH