RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 4 – INITIAL START-UP

Page 58 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

4.2.3 Accessing the Analyzer Probe Port

The unit contains a 1/8” NPT port at the rear of the exhaust manifold. This port is located above
the condensate drain connection as shown in Figure 4-2. Prepare the port for the combustion
analyzer probe as follows:

Accessing Analyzer Probe Port

1. Refer to Figure 4-2 and remove the 1/8” NPT plug from the rear of the exhaust manifold.

2. If necessary, adjust the stop on the combustion analyzer probe so it will extend mid-way into

the flue gas flow. DO NOT install the probe at this time

Figure 4-2: Analyzer Probe Hole Location

4.2.4 Connecting a Multimeter to the Flame Detector

During Combustion Calibration, the flame strength generated by the flame detector is measured
using a multimeter set to the µA scale. The flame detector is mounted on the flange of the blower
side intake manifold as shown in Figure 4-3.

Proceed as follows to set up the multimeter to measure the flame strength current:

EXHAUST

MANIFOLD

VENT PROBE
PORT WITH 1/8”
NPT PLUG

CONDENSATE
DRAIN PORT