CHAPTER 8 – WATER HEATER MANAGEMENT

Page 124 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

WHM MENU

See section 8-6 for a range of choices and the default values.

ITEM

MENU LEVEL &

OPTION

DESCRIPTION

30

MB Head Temp En

Enable or disable the Modbus Header Temp sensor

31

WHM Header Temp

Display the Header Sensor

32

Mdbus Temp Units

Modbus temp unit format (˚F or ˚C)

33

Header Temp Addr

Modbus header Temp address.

34

Header Tmp Point

Modbus point to read the header temp register point

35

MB Outdr Sens En

Enable or disable the Modbus Outdoor Temp sensor

36 WHM

Outdr

Temp

Display Outdoor temp value

37

Outdoor Tmp Addr

Modbus Outdoor Temp address

38

Outdoor Tmp Pnt

Modbus point to read the Outdoor Temp register point

39

Err Threshold

Max allowable comm errors before a comm. fault is invoked.

40

Comm Address

Set the Comm Address for the unit (This option also available in setup menu)

41

1 WHM Units 8

This menu item shows the current status for each unit controlled by WHM (8
max.). The characters displayed are defined as:
- = Off Line, * = Not available (fault, etc.), 0 = Off, 1 = On,
A = Lead On, a = Lead Off, B = Lag On, b = Lag Off

The following example shows the status of 5 units being controlled by WHM:

1 WHM Units 8
_ 1_ _0_ _1_ _*_ _A_ _b_ ___ ___

Where: Unit 1 & 3 = On, Unit 2 = Off, Unit 4 = Not available,
Unit 5 = Lead On, Unit 6 = Lag Off

NOTE

The WHM Nxt On VP and WHM Nxt Off VP will determine how tight a range the
temperature is controlled over and how quickly the system responds to a change in load.
A narrow difference between Nxt On VP and WHM Nxt Off VP will make the system more
responsive to load changes.

8.8 WHM HARDWARE INSTALLATION & SET-UP INSTRUCTIONS

The following sections provide the basic installation and set-up instructions for implementing a
Water Heater Management System (WHM) to control up to eight (8) AERCO RECONRECON
Water Heaters. The installation procedure included in Chapter 2 is repeated here to avoid
unnecessary referencing.