RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 2 – INSTALLATION

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 27 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

Condensate Trap Installation

1. Connect the condensate trap inlet to the exhaust manifold drain connection using the

appropriate piping components (nipples, reducers, elbows, etc.) for the heater installation
site. An example is shown in Figure 2-9.

2. At the condensate trap outlet, install a 3/4” NPT nipple.

3. Connect a length of 1” I.D. polypropylene hose to the trap outlet and secure with a hose

clamp.

4. Route the hose on the trap outlet to a nearby floor drain.

If a floor drain is not available, a condensate pump can be used to remove the condensate to
drain. The maximum condensate flow rate is 5 GPH for the RECON 500 and 8 GPH for the
RECON 1000. The condensate drain trap, associated fittings and drain line must be removable
for routine maintenance.

--WARNING! -

Use PVC, stainless steel, aluminum or polypropylene for
condensate drain piping (Figure 2-9). DO NOT use carbon or
copper components.

Figure 2-9: Sample Condensate Trap Installation

NOTE

Housekeeping pad should

not extend under the

condensate assembly

EXHAUST
MANIFOLD

3/4" NPT
NIPPLES

ADAPTER WITH
INTERNAL THREADS

TOP COVER
THUMB SCREWS

TO FLOOR DRAIN

UNION

CONDENSATE
TRAP

ADAPTER THUMB SCREW

1” I.D. HOSE
& CLAMP