CHAPTER 5 – SAFETY DEVICE TESTING

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 71 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

Figure 5-2: Temperature Limit Switch Setting

5.6 INTERLOCK TESTS

The unit is equipped with two interlock circuits called the Remote Interlock and Delayed
Interlock. Terminal connections for these circuits are located in the I/O Box (Figure 2-12) and
are labeled REMOTE INTL’K IN and DELAYED INTL’K IN. These circuits can shut down the
unit in the event that an interlock is opened. These interlocks are shipped from the factory
jumpered (closed). However, each of these interlocks may be utilized in the field as a remote
stop and start, an emergency cut-off, or to prove that a device such as a pump, gas booster, or
louver is operational.

5.6.1 Remote Interlock Test

Remote Interlock Test

1. Remove the cover from the I/O Box and locate the REMOTE INTL’K IN terminals (see

Figure 2-12).

2. Start the unit in the Manual Mode and set the valve position between 25% and 30%.

3. If there is a jumper across the REMOTE INTL’K IN terminals, remove one side of the

jumper. If the interlock is being controlled by an external device, either open the interlock
via the external device or disconnect one of the wires leading to the external device.

4. The unit should shut down and display INTERLOCK OPEN.

5. Once the interlock connection is reconnected, the INTERLOCK OPEN message should

automatically clear and the unit should restart.

MANUAL RESET (NON-ADJUSTABLE)

OVER-TEMPERATURE LIMIT SWITCH

AUTOMATIC RESET (ADJUSTABLE)

TEMPERATURE OVER- LIMIT SWITCH