RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 2 – INSTALLATION

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 23 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

2.6 INSTALLING THE TEST HOSE BIB AND DRAIN VALVE

A Test Hose Bib must be installed upstream of the hot water outlet shut off valve, This is
required for startup and testing (see Figure 2-5 A). The pipe diameter should be a minimum of
3/4". The Test Hose Bib cannot be omitted.

Figure 2-5 A: Test Hose Bib Location – Left Side View

The drain valve, which is shipped loose, must be installed on the cold water inlet. It is suggested
that it be installed on the right side of the unit, on a nipple attached to the building recirculation
inlet (see Figure 2-5 B), with a cap on the end. It could instead be installed on the cold water
inlet pipe, on the left side of the unit.

Figure 2-5 B: Drain Valve Location – Right Side View

TO DRAIN

TEST

HOSE BIB

HOT

WATER

OUT

TEST HOSE BIB

CONNECTION

HOT WATER SHUTOFF VALVE

BUILDING
RECIRCULATION
INLET

COLD

WATER

INLET

DRAIN VALVE

NIPPLE AND CAP