Start Sequence – Continued

4. Next, the blower proof switch on the Air/Fuel Valve (Figure 3-5) closes. The display will

show Purging and indicate the elapsed time of the purge cycle in seconds.

Figure 3-5: Blower Proof Switch

5. Upon completion of the purge cycle, the Control Box initiates an ignition cycle and the

following events occur:

(a)

The Air/Fuel Valve rotates to the low-fire ignition position and closes the ignition

switch. The dial on the Air/Fuel Valve (Figure 3-6) will read between 25 and 35 to
indicate that the valve is in the low-fire position.

(b)

The igniter relay is activated and provides ignition spark.

(c)

The gas Safety Shut-Off Valve (SSOV) is energized (opened) allowing gas to flow into

the Air/Fuel Valve.

BLOWER

PROOF

SWITCH

AIR/FUEL
VALVE

BLOCKED
INLET
SWITCH

AIR IN

TO BLOWER

GAS IN

STEPPER MOTOR

TRANSPARENT COVER