RECON Water Heaters Installation, Operation & Maintenance Manual

APPENDIX A – RECON MENU ITEM DESCRIPTIONS

Page 142 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

Table A-5: CALIBRATION MENU ITEM DESCRIPTIONS

See section 3-8 for a range of choices and the default values.

MENU LEVEL & OPTION

DESCRIPTION

22

Water Temp Reset

Allows the Water Temperature Reset function to be set to Auto or
Manual.

23

Gas Press Reset

Allows the Gas Pressure Reset function to be set to Auto or Manual.

24

Min Off Time

Allows the minimum Off time to be set from 0 to 10 minutes.

25

Heatr Tuning Dsp

Allows Heater Tuning Display to be Enabled or Disabled.

26

Heatr Bkpt Dsp

Allows Heater Breakpoint Display to be Enabled or Disabled. When
Enabled, Breakpoints can be viewed and/or changed.

27 Stop

Level

Allows the Stop Level to be set to a valve position ranging from 0% to
the presently set Start Level.

28

Start Level

Allows the Start Level to be set to a valve position ranging from the
presently set Stop Level to a maximum of 40%.

SKIP FEATURE:
Items 29 – 31 embody a feature that allows the user to define a Fire Zone the C-More will avoid. In
the rare instance when a unit emits an objectionable noise at a certain Fire Rate and no other remedy
solves the problem, a Fire Rate skip zone may be defined to command the C-More to Skip-Over the
defined Fire Rate.

29

– Skip Range CNTR Defines the Center (Fire Rate) of the skip band.

30

– Skip Range Span

Defines the + and – band of the Skip Zone Size.

31

– Skip Speed

Defines the speed (Seconds/Fire Rate) at which the band will be
skipped.

O2 Settings:
Items 32 – 34 allow calibration of oxygen readings.

32 – O2 Gain

Range = 920 to 1126. (Unity Gain, No Mods)

33 – O2 Offset

Range = -3.0 to +3.0.

34 – O2 Sensor

Enables the O2 Sensor

35

Cal Temp Sensors

Allows calibration of the temperature sensor

Temperature Channel Offset:
Items 36 – 41 embody the feature, which allow the user to field calibrate all six temperature channels
by entering an offset corresponding to the desired temperature channel.

36 – FFWD Temp Offset Range = -20ºF to +20ºF

37 – Exhst Tmp Ofset

Range = -20ºFto +20ºF

38 – Outdr Air Offset

Range = -20ºF to +20ºF

39 – Inlet Air Offset

Range = -20ºF to +20ºF

40 – Inlet Wtr Offset

Range = -20ºF to +20ºF

41 – Outlet Wtr Offset

Range = -20ºF to +20ºF