RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

Page 48 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

24 Temp

Gov

Enable or Disable

Enable

25 GOV

Limit-5

0 100

30

26 GOV

Limit-7

0 100

20

27 GOV

Limit-10

0 100

15

28 GOV

Limit-12

0 100

10

29 GOV

Limit-15

0 100

5

30 PID

Output

0%

100%

Read Only Value

31 P

Output

0%

100%

Read Only Value

32 I

Output

0%

100%

Read Only Value

33 D

Output

0%

100%

Read Only Value

34 Reset

Defaults

Yes No

No

3.8 CALIBRATION MENU

The Calibration Menu is used by Factory Trained Service personnel to adjust or reset the
parameters listed below.

A full description of each item appears in Table A-5 of Appendix A – Recon Menu Item
Descriptions.

Table 3-6: Calibration Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

1 Stepper

Fbk

Cal 0%

Cal 100%

Verify 50%

Cal 0%

2

Purge Timer

5 sec.

60 sec

Depends on unit type/size

3

Post Purge Timer

0 sec.

60 sec.

0 sec.

4

IGN Position

5%

60%

Depends on unit type/size

5

FFWD Temp Disply

Enabled or Disabled

6

Outlet Tmp Dsply

Enabled or Disabled

7

Inlet Tmp Dsply

Enabled or Disabled

8

Valv Pos Out Dsp

Enabled or Disabled

9

Exhaust Tmp Dsp

Enabled or Disabled

10 VP Up Rate

0.5

60.0

Depends on unit type/size

11 VP Down Rate

0.5

60.0

Depends on unit type/size

12 Purge Blwr Offst

-1.0

8.0

Depends on unit type/size