RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 6 – MAINTENANCE

Page 86 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

Fireside Inspection – Continued

BURNER, INTAKE AND EXHAUST MANIFOLDS – EXPLODED

Figure

6-6. Combustion Chamber Gasket Locations

IMPORTANT

During reassembly, apply high-temperature, anti-seize lubricant to
the threads of the igniter and grounding screw. Also, ensure that the
igniter are properly positioned and are not contacting other
components. Torque the igniter to 15 ft-lbs.

18. Beginning with the exhaust manifold assembly removed in Step 14, reinstall all the

components in the reverse order that they were removed.

--WARNING! -

The manifold-to-heat exchanger gasket must be held in place with
High Temp RTV Silicone sealant. The exhaust manifold must be
carefully raised into place, centered, and leveled to insure the
gasket makes a good seal between the manifold and heat
exchanger.

19. Reinstall the exhaust vent onto the exhaust manifold using a High Temp Red RTV silicon

sealant, such as sealants available from Permatex or Loctite.

BURNER FLANGE GASKET

(P/N GP-18899)

BURNER

CONDENSATE

SHIELD

BURNER
ASSEMBLY

INTAKE MANIFOLD

EXHAUST

MANIFOLD

BURNER FLANGE GASKET

(P/N GP-18899)

SHIELD

GASKET

(P/N 81197)