RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 4 – INITIAL START-UP

Page 64 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

4.4.1 Setting the Outlet Water Temperature Setpoint

The setpoint temperature of the unit may be changed using the following steps. However, once a
setpoint has been changed, recalibration may be necessary.

To adjust the unit’s setpoint, proceed as follows:

Setting Outlet Water Temperature Setpoint

1. Press the MENU key until Configuration Menu is displayed.

2. Press the ▲ or ▼ arrow key until Internal Setpt is displayed along with the present setpoint

temperature.

3. To change the setpoint, press the CHANGE key. The display will begin to flash.

4. Press the ▲ or ▼ arrow key until the desired setpoint is displayed.

5. Press the ENTER key to save the change.

4.4.2 Minimum Load Adjustment

With the unit in operation, check the temperature control at minimum load as follows:

Minimum Load Adjustment

1. While monitoring the VALVE POSITION bar-graph, create a minimum load on the system that

will yield a steady valve position between 25% and 35%.

NOTE

It may be desirable to shut off the outlet valve and use the hose bib
(see Figure 2-4) to simulate a minimum flow load condition

.

2. Wait several minutes to allow the outlet temperature to stabilize under load conditions.

3. Once stabilized, the OUTLET TEMPERATURE display should read no more than 2 to 3

degrees above the unit’s setpoint.

4. If the outlet temperature is stabilized, proceed to the Maximum Load Adjustment procedure in

section 4.4.3. If the temperature is not stabilized, proceed to step 5.

5. Press the MENU key and select the Tuning Menu.

6. Press the ▲ or ▼ arrow key until Min Load Adj is displayed.

7. Press the CHANGE key. The display will begin to flash.

8. Raise or lower the minimum load adjustment in increments of one or two using the ▲ or ▼

arrow key. Increasing this value will increase outlet water temperature, while decreasing it
will decrease outlet water temperature.

9. Press ENTER to save the change. Allow time for the system to stabilize between

adjustments

10. Repeat steps 5 through 9 as needed until the temperature is stabilized at no more than 2 to 3

degrees above the unit’s setpoint.