RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 5 – SAFETY DEVICE TESTING

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 73 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

Flame Fault Tests – Continued

11. Open the valve previously closed in step 8.

12. Press the CLEAR button. The unit should restart and fire.

Figure 5-3: Manual Gas Shut-Off Valve Location (RECON 1000 Shown)

5.8 AIR FLOW FAULT TESTS

These tests check the operation of the Blower Proof Switch and Blocked Inlet Switch shown in
Figure 5-4.

Air Flow Fault Tests

1. Disable the blower output drive voltage as follows:

(a)

Press the MENU key until CONFIGURATION MENU is displayed.

(b)

Press the ▲ arrow key until the ANALOG OUTPUT function is displayed, then press
the CHANGE key.

(c)

Press the ▼ arrow key until OFF is displayed, then press the ENTER key.

2. Start the unit in the Manual Mode at a valve position of 25%.

3. The unit should shut down and execute an IGNITION RETRY cycle by performing the

following steps:

(a)

The unit will execute a 30 second re-ignition delay and display WAIT RETRY PAUSE.

(b)

The unit will then execute a standard ignition sequence and display WAIT IGNITION
RETRY

.

4. The unit should perform two IGNITION RETRY cycles and then shut down on the third

successive ignition attempt. The unit will display AIRFLOW FAULT DURING PURGE.

5. Re-enable the blower output drive voltage by performing the following steps:

(a)

Press the MENU key until CONFIGURATION MENU is displayed.

(b)

Press the ▲ arrow key until the ANALOG OUTPUT function is displayed, then press
the CHANGE key.

(c)

Press the ▲ arrow key until VALVE POSITION 0-10V is displayed, then press the
ENTER key.

MANUAL

SHUTOFF

VALVE