background image

RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

Page 46 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

Table 3-4: Configuration Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

1

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F

2

Unit Type

RECON WtrHeater

RECON WtrHeater

3

Unit Size

500 MBH, 1000 MBH

500 MBH

4

Fuel Type

Natural Gas, Propane

Natural Gas

5

Water Heater Mode

Constant Setpoint, Remote

Setpoint,

Constant Setpoint

6

Remote Signal
(If Mode = Remote Setpoint,
Direct Drive or Combination)

4 – 20 mA/1 – 5V

0 -20 mA/0 – 5V

PWM Input (Legacy BMS)

Network

4 – 20 mA,

1-5V

7

Outdoor Sensor

Enabled or Disabled

Disabled

8

System Start Tmp
(If Outdoor Sensor = Enabled)

30°F 100°F 60°F

9

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

10

Setpt Hi Limit

Setpt Lo Limit

190°F

150°F

11

Temp Hi Limit

40°F

200°F

160°F

12

Max Valve Position

40%

100%

100%

13

Pump Delay Timer

0 min.

30 min.

0 min.

14

Aux Start On Dly

0 sec.

120 sec.

0 sec.

15

Failsafe Mode

Shutdown or Constant Setpt

Shutdown

16

* Analog Output

Off, Setpoint, Outlet Temp, Valve

Pos 4-20mA, valve Pos 0-10v

* Valve Pos 0-10v

17

Low Fire Timer

2 sec.

600 sec.

2 sec.

18

Setpt Limiting

Enabled or Disabled

Disabled

19

Setpt Limit Band

0°F

10°F

5°F

20

Network Timeout

5 Sec

999 Sec

30 Sec

21 Shutoff

Dly

Temp

0

25

8

22 Demand

Offset

0

25

5

23

Deadband High

0

25

0

24 Deadband

Low

0

25

0

25

IGST Version

V2.00 or Lower

V2.02

0

26

IGN Timing Setting

4 Sec

7 Sec

-

-WARNING! -

* DO NOT CHANGE the Analog Output menu item from its

default setting (Valve Position 0-10V).