RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 2 – INSTALLATION

Page 20 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

2.5 WATER INLET AND OUTLET PIPING

The locations of the 2" NPT cold water inlet and hot water outlet piping connections are shown
in Figure 2-3a. Flow rates through the unit are limited to 50 gpm continuous.

Shut-off valves and union connections must be installed in the inlet and outlet lines for
maintenance. The use of dielectric unions is recommended.

NOTE

All piping must be arranged so that it does not interfere with
removal of any covers, inhibit service or maintenance, or prevent
access between the unit and walls, or another unit.

Figure 2-3a: Inlets and Outlets (With Covers)

4” AIR
INLET

HOT WATER
OUTLET – 2” NPT
(Field Installed)

COLD WATER

INLET 2” NPT

GAS INLET

1-1/4"

EXHAUST

MANIFOLD

BUILDING

RECIRCULATION

LINE

2” NPT