AERCO RECON 1000 User Manual

Page 102

Advertising
background image

RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 7 – TROUBLESHOOTING GUIDE

Page 102 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

TABLE 7-1: WATER HEATER TROUBLESHOOTING –

Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

AIRFLOW FAULT
DURING PURGE

1.

Blower not running or running too slow

2.

Defective Air Flow Switch

3.

Blocked Air flow Switch

4.

Blocked Blower inlet or inlet ductwork.

5.

No voltage to switch from control box.

6.

PROBABLE CAUSES from 3 to 12 for
AIRFLOW FAULT DURING IGNITION
applies for this fault

1.

Start the unit. If the blower does not run check the blower solid
state relay for input and output voltage. If the relay is okay,
check the blower.

2.

Start the unit. If the blower runs, check the airflow switch for
continuity. Replace the switch if there is no continuity.

3.

Remove the air flow switch and inspect for signs of blockage,
clean or replace as necessary.

4.

Inspect the inlet to the combustion blower including any
ductwork leading up to the combustion blower for signs of
blockage.

5.

Measure for 24 VAC during start sequence from each side of
the switch to ground. If 24VAC is not present refer to qualified
service personnel.

6.

See CORRECTIVE ACTIONS from 3 to 12 for AIRFLOW
FAULT DURING IGNITION.

AIRFLOW FAULT
DURING RUN

1.

Blower stopped running due to thermal
or current overload

2.

Blocked Blower inlet or inlet ductwork

3.

Blocked airflow switch

4.

Defective airflow switch

5.

Combustion oscillations

6.

PROBABLE CAUSES from 3 to 16 for
AIRFLOW FAULT DURING IGNITION
applies for this fault

1.

Check combustion blower for signs of excessive heat or high
current draw that may trip thermal or current overload devices.

2.

Inspect the inlet to the combustion blower including any
ductwork leading up to the combustion blower for signs of
blockage.

3.

Remove the airflow switch and inspect for signs of blockage,
clean or replace as necessary.

4.

Measure the airflow switch for continuity with the combustion
blower running. If there is an erratic resistance reading or the
resistance reading is greater than zero ohms, replace the
switch.

5.

Run unit to full fire. If the unit rumbles or runs rough, perform
combustion calibration.

6.

See CORRECTIVE ACTIONS from 3 to 16 for AIRFLOW
FAULT DURING IGNITION.

Advertising
This manual is related to the following products: