Lwco capacitor electrical short test – continued – AERCO RECON 1000 User Manual

Page 96

Advertising
background image

RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 6 – MAINTENANCE

Page 96 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

LWCO Capacitor Electrical Short Test – Continued

2. Remove the Shell Harness Cable (male) connector from the P-5 (female) connector on the

rear panel of the C-More controller (see Figure 6-13).

Figure 6-13: Removing Shell Harness Cable from P5 Conn. on C-More Rear Panel

3. Using an ohmmeter, connect one ohmmeter probe to the LWCO capacitor terminal on the

unit shell as shown on left in Figure 6-14.

4. Connect the second ohmmeter probe to Pin #6 of Shell Harness Connector (removed

from the C-More controller) as shown on right in Figure 6-14.

Figure 6-14: Connecting Ohmmeter between LWCO Probe & Shell Harness Cable

P1

P2

P3

P4

P5

P6

SHELL HARNESS

CONNECTOR

(19 PIN)

GAS TRAIN HARNESS

CONNECTOR

(9 PIN)

A/F VALVE HARNESS

CONNECTOR

(16 PIN)

SENSOR

HARNESS

CONNECTOR

(7 PIN)

INTERLOCK HARNESS

CONNECTOR

(16 PIN)

TO INPUT/OUTPUT (I/O)

BOX

EXT. SENSOR/COMM

HARNESS CONNECTOR

(24 PIN)

TO INPUT/OUTPUT (I/O)

BOX

Unplug Shell

Harness Cable

from

P5 Connector

Connect 1

st

Lead to LWCO Terminal

Connect 2

nd

Lead to PIN #6

19-Pin Shell Harness Cable

Connector

LWCO Probe Assembly Connector

Ohmmeter