Appendix a – recon menu item descriptions – AERCO RECON 1000 User Manual

Page 135

Advertising
background image

RECON Water Heaters Installation, Operation & Maintenance Manual

APPENDIX A – RECON MENU ITEM DESCRIPTIONS

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 135 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

APPENDIX A – RECON MENU ITEM DESCRIPTIONS

Table A-1: Operating Menu Item Descriptions

Table A-1: OPERATING MENU ITEM DESCRIPTIONS

See section 3-4 for a range of choices and the default values.

MENU LEVEL & OPTION

DESCRIPTION

1 Active

Setpoint

This is the setpoint temperature to which the control is set
when operating in the Constant Setpoint or Remote Setpoint
Mode. When in the Constant Setpoint Mode, this value is
equal to the Internal Setpoint setting in the Configuration Menu.
When in the Remote Setpoint Mode, this value is the setpoint
equivalent to the remote analog signal supplied to the unit

2

Inlet Temp

Displays Inlet Water Temperature

3

Air Temp

For monitoring purposes only

4

Outdoor Temp

Displayed only if outdoor sensor is installed and enabled.

5

Valve Position In

Desired input valve position. This would normally be the same
as the valve position shown on the bargraph when the heater is
operating.

6

Exhaust Temp

Displays Exhaust Gas Temperature

7

Valve Position Out

Displays actual real time Valve Position

8

FFWD Temp

Displays Feed Forward Water Temperature

9

Flame Strength

Displays flame strength from 0% to 100%.

10 Oxygen Level

Displays the Oxygen Level of combustion exhaust gasses

11 Ignition

Time

Displays the elapsed time between confirmation of gas valve
opening (POC) until a stable flame is detected

12 SSOV Time to OPN

Displays the elapsed time between 120VAC being applied to
the Gas Valve and confirmation of gas valve opening (POC)

13 Run Cycles

Displays the total number of run cycles from 0 to 999,999.

14 Run Hours

Displays total run time of unit in hours from 0 to 9,999,999.

15 Fault Log

Displays information on the last 20 faults (0 – 19).