RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 5 – SAFETY DEVICE TESTING

Page 70 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

Low Water Level Fault Test – Continued

11. Press the CLEAR button to reset the FAULT LED and clear the displayed error message.

12. Set the ON/OFF switch to the ON position. The unit is now ready for operation.

5.5 WATER TEMPERATURE FAULT TEST

A high water temperature fault is simulated by adjusting the automatic over-temperature switch.
This switch is accessible from the front of the unit as shown in Figure 5-2.

Water Temperature Fault Test

1. Start the unit in the normal operating mode. Allow the unit to stabilize at its setpoint.

2. Lower the adjustable over-temperature switch setting to match the displayed OUTLET

TEMPERATURE.

3. Once the adjustable over-temperature switch setting is approximately at, or just below, the

actual outlet water temperature, the unit should shut down. The FAULT indicator should
start flashing and a HIGH WATER TEMP SWITCH OPEN fault message should be
displayed. It should not be possible to restart the unit.

4. Reset the adjustable over-temperature switch to its original setting.

5. The unit should start once the adjustable temperature limit switch setting is above the actual

outlet water temperature.

NOTES

The manual (non-adjustable) Over Temp Limit switch is
calibrated to trip if the discharge water exceeds 190° F. Testing
of this device must be done by authorized personnel only.