Series 3L Indicators

17

4.3 FM and Alarm Units

Series 3L indicators supplied to Function code FM are
FM approved.

Series 3L indicators supplied to Function code DN are
approved to EN14597.

The instrument label is marked accordingly.

In these instruments, the alarm operating the AA relay
output is set to inverted and latching. This function
cannot be altered.

When the instrument is configured using the Quick
Start codes (section 3.1), Alarm 1 is used to operate
both Outputs 1 and 4 (AA relay). The Quick Start
configuration for the AA relay will enable and configure
Alarm 4 but Alarm 4 will not be used to operate Output
4.

!

If Quick Start is used to configure Alarm 1 as

a high alarm and Alarm 4 as a low alarm, then the
resulting configuration will be that the high alarm 1 is
used to drive both outputs 1 and 4. The low alarm 4
will not be connected to any output.

Further details on latching and blocking alarms can be
found in section 9.1.

4.4 Recipes

Not Applicable to this Instrument