7.2 Output Channel 3 (OP-3) – Series 3L Indicators

Output 3 is always a form A relay in the indicator and is connected to terminals 3A and 3B. It is typically used to
provide external indication of alarms.

Output 3 is configured using the parameters in the following table:-

OUTPUT LIST 3 ‘o p -3 ’

Name

Scrolling Display

Parameter

Description

Value

Default

Access

Level

3.I D

I/O 3 TYPE

Displays the type of
output

ReLy Relay output

ReLy

Read
only

3.FUNC

I/O 3 FUNCTION

The function may be
turned off, otherwise
set to

d.out

none

Disabled. If disabled no further
parameters are shown

none

Conf

d.out Digital output

3.SRC.A

I/O 3 SOURCE A

Selects the source of
an event which will
operate the output
relay

The output status is
the result of an OR of
Src A, Src B, Src C,
and Src D

Up to four events can,
therefore, operate the
output
See section 7.2.2.

none No event connected to the

output

none

Conf

3.SRC.B

I/O 3 SOURCE B

1.--- Alarm 1

The --- indicates the
alarm type. If the
alarm is not
configured
AL.(Alarm no) is
shown

2.--- Alarm 2

3.SRC.C

I/O 3 SOURCE C

3.--- Alarm 3
4.--- Alarm4

3.SRC.D

I/O 3 SOURCE D

ALL.A All alarms. Logical AND of

alarms 1 to 4.

nw.AL Any new alarm
Pwr.f Power fail.
O.rng Output relay operates if the

indicator input is over range

sbr

Sensor break alarm

3.SENS

I/O 3 SENSE

To configure the
sense of the output
channel.
See also section 7.2.1

nor
Inv

Normal
Inverted

nor

Conf