Technical specification – Super Systems 3L Series User Manual

Page 51

Advertising
background image

Series 3L Indicators

51

13. TECHNICAL SPECIFICATION


General

Temperature limits Operation: 0 to 55°C (32 to 131°F),

Storage: -10 to 70°C (14 to 158°F)

Humidity limits

Operation: RH: 5 to 90% non-condensing

Storage: RH: 5 to 90% non-condensing

Panel sealing

IP 65, Nema 4X

Shock

BS EN61010

Vibration

2g peak, 10 to 150Hz

Altitude

<2000 metres

Atmospheres

Not suitable for use above 2000m or in
explosive or corrosive atmospheres.

Electromagnetic
compatibility
(EMC)

BS EN61326

Electrical safety

BS EN61010 Installation cat. II; Pollution
degree 2

Installation
category II

The rated impulse voltage for equipment
on nominal 230V supply is 2500V

Pollution degree 2 Normally only non conductive pollution

occurs. Occasionally, however, a
temporary conductivity caused by
condensation shall be expected.

Physical

Series 3L

Panel mounting

1/4 DIN

Weight grams

420

Dimensions mm

96W x 96H x
90D

Panel cut-out
dimensions mm

92W x 92H

Operator interface

Type

LCD TN with backlight

Main PV display

Series 3L

4 digits
green

Lower display

5 character
starburst,
green

Status beacon

Units, outputs, alarms, active setpoint

Power requirements

Series 3L

100 to 240Vac, -15%, +10%
48 to 62Hz, max 8W
24Vac, -15%, +10%
24Vdc, -15%, +20%, +5% ripple voltage,
max 8W

Approvals

CE, cUL listed (file ES7766), Gost, FM,
EN14597TW approval number TW1222.

Transmitter PSU

Isolation

264Vac double insulated

Output Voltage

24Vdc, 20mA

Communications: serial communications option

Protocol

Modbus RTU slave

Modbus RTU Master broadcast (1
parameter)

Isolation

264Vac double insulated

Transmission
standard

EIA485 2-wire

Transmission
standard

EIA485 2-wire

Process Variable Input

Calibration accuracy <+0.25% of reading +1LSD

(1)

Sample rate

9Hz (110mS)

Isolation

264Vac double insulated from the PSU
and communications

Resolution (µV)

< 0.5µV with 1.6s filter (mV range)

< 0.25µV with 1.6s filter (Volts range)

Resolution (effective
bits)

>17 bits

Linearisation
accuracy

<0.1% of reading

Drift with
temperature

<50ppm (typical) <100ppm (worst case)

Common mode
rejection

48 - 62 Hz, >-120db

Series mode
rejection

48 - 62 Hz, >-93db

Input impedance

100M

(200KΩ on volts range C)

Cold junction
compensation

>30 to 1 rejection of ambient
temperature

External cold
junction

Reference of 0

O

C

Cold junction
accuracy

<+1

o

C at 25

o

C ambient

Linear (process)
input range

-10 to 80mV, 0 to 10V with external
potential divider module 100K

Ω/806Ω

Thermocouple Types K, J, N, R, S, B, L, T, C, custom

download

(2)

RTD Type

3-wire, Pt100 DIN43760

Bulb current

0.2mA

Lead compensation

No error for 22 ohms in all 3 leads

Input filter

Off to 100 seconds

Zero offset

User adjustable over the full display
range

User calibration

2-point gain & offset

Notes

(1) Calibration accuracy quoted over full ambient operating
range and for all input linearisation types.

(2) Contact SSI for details of availability of custom downloads for
alternative sensors.

Sample time:

9hz (110ms)

Isolation:

264Vac double isolation from the PSU
and communications

Excitation:

10Vdc +7%

Sensitivity:

1.4 to 4mV/V

Input span:

-27% to +127% of full scale (approx. –