5 parameter modbus addresses, Parameter modbus addresses – Super Systems 3L Series User Manual

Page 43

Advertising
background image

Series 3L Indicators

43

11.5 Parameter Modbus Addresses

Parameter
Mnemonic

Parameter Name

Modbus

Address

(Decimal)

PV.IN

PV (Temperature) Input Value (see
also Modbus address 203 which
allows writes over Modbus to this
variable).

1

RNG.LO

Input Range Low Limit

11

RNG.HI

Input Range High Limit

12

A1.---

Alarm 1 Threshold

13

A2.---

Alarm 2 Threshold

14

Cal offset 4

26

LOC.t

Local Trim – added to the remote
setpoint to compensate for local
temperature variations in a control
zone.

27

A1.HYS

Alarm 1 Hysteresis

47

Cal point 4

66

Cal point 3

67

A2.HYS

Alarm 2 Hysteresis

68

A3.HYS

Alarm 3 Hysteresis

69

A4.HYS

Alarm 4 Hysteresis

71

StAt




Instrument Status. This is a bitmap:
B0 – Alarm 1 Status
B1 – Alarm 2 Status
B2 – Alarm 3 Status
B3 – Alarm 4 Status
B5 – Sensor Break Status
B10 – PV Overrange (by > 5% of
span)
B12 – New Alarm Status
In each case, a setting of 1 signifies
‘Active’, 0 signifies ‘Inactive’.

75




A3.---

Alarm 3 Threshold

81

A4.---

Alarm 4 Threshold

82

Di.IP

Digital Inputs Status. This is a
bitmap:
B0 – Logic input 1A
B1 – Logic input LA
B2 – Logic input LB
B7 – Power has failed since last
alarm acknowledge
A value of 1 signifies the input is
closed, otherwise it is zero. Values
are undefined if options are not
fitted or not configured as inputs.

87

FILT.T

Input Filter Time

101

Home

Home Display.
0 – Standard PV display
4 – PV and Alarm 1 setpoint
6 – PV only
7 – PV and Alarm 1 setpoint read
only

106

-

Instrument version number. Should
be read as a hexadecimal number,
for example a value of 0111 hex is
instrument V1.11

107

-

Static message

108

-

Instrument type code.

122

HIGH

Peak high

126

LOW

Peak low

127

ADDR

Instrument Comms Address

131

PV.OFS

PV Offset

141

C.Adj

Calibration Adjust

146

IM

Instrument mode
0 – Operating mode - all algorithms
and I/O are active
1 – Standby - control outputs are off
2 – Config Mode - all outputs are
inactive

199

COLOR

Colour change
Green –
Red –
Green normal/Red on alarm –

200

MV.IN

Input value in millivolts

202

PV.CM

Comms PV Value. This may be
used to write to the Process
Variable (temperature) parameter
over Modbus when a linearisation
type of ‘Comms’ is selected,
allowing the instrument to control to
externally derived values.
If sensor break is turned on, it is
necessary to write to this variable
once every 5 seconds. Otherwise a
sensor break alarm will be triggered
as a failsafe. If this is not required,
turn sensor break off.

203

204

CJC.IN

CJC Temperature

215

TARE

Tare enable
Off –
On –
Fail -

223

SBR

Sensor Break Status (0 = Off, 1 =
Active)

258

NEW.AL

New Alarm Status (0 = Off, 1 =
Active)

260

Alarm latch status

261

Ac.All

Acknowledge all alarms (1 =
Acknowledge

274

A1.STS

Alarm 1 Status (0 = Off, 1 = Active)

294

A2.STS

Alarm 2 Status (0 = Off, 1 = Active)

295

A3.STS

Alarm 3 Status (0 = Off, 1 = Active)

296

A4.STS

Alarm 4 Status (0 = Off, 1 = Active)

297

Alarm 1 inhibit

298

Alarm 2 inhibit

299

Alarm 3 inhibit

300

Alarm 4 inhibit

301

REC.NO

Recipe to Recall

313

STORE

Recipe to Save

314

Lev2.P

Level 2 Code

515

UNITS

Display Units
0 – Degrees C
1 – Degrees F
2 – Kelvin
3 – None
4 – Percent

516

Lev3.P

Level 3 Code

517

Conf.P

Config Code

518

Cold

If set to 1 instrument will reset to
factory defaults on next reset or
power cycle.

519

DEC.P


Decimal Point Position
0 – XXXX.
1 – XXX.X
2 – XX.XX

525


STBY.T

Standby Type
0 – Absolute Alarm Outputs Active

530

Advertising