Super Systems 3L Series User Manual

Page 52

Advertising
background image

Operations Manual

Series 3L

52

10mV to +5mV):

Zero balance:

+ 25% of full scale

Tare:

+ 25% of full scale

Resolution (mV):

0.3mV/V(typical) with 1.6s filter

Resolution
(effective bits):

14.3 bits

Drift with
temperature:

<100ppm/°C of full scale

Common mode
rejection:

48-62Hz, >-120db

Series rejection:

48-62Hz, >-60db

Input filter:

Off to 100s

AA relay

Type

Form C changeover

Rating

Min: 100mA @ 12Vdc,
Max: 2A @ 264Vac resistive

Functions

Alarms or events

Digital input A/B

Contact closure

Open >600

Ω Closed <300Ω

Input current

<13mA

Isolation

None from PV or system
264Vac double insulated from PSU and
communications

Functions

Includes alarm acknowledge, keylock,
alarm inhibit, freeze display, tare, auto
zero, peak reset

Relay output channels
Type

OP1, OP3

Form A (normally open)

AA

Form C changeover

Rating

Min: 100mA @ 12Vdc, Max: 2A @
264Vac resistive

Functions

Alarms or events

Software features

Alarms

Number

4

Type

Absolute high and low, rate of change
(rising or falling)

Latching

Auto or manual latching, non-latching, event
only

Output
assignment

Up to four conditions can be assigned to
one output

Custom messages

Number

15 scrolling text messages

Number of
characters

127 characters per message max

Languages

English, German, French, Spanish, Italian

Selection

Active on any parameter status using

conditional command

Recipes

Number

5 with 19 parameters

Selection

HMI interface, communications or dig. IO

Other features

Scrolling text

Parameter help, custom messages

Display filter

Off to zero last 2 digits

Peak monitor

Stores high and low values

FM

Alarm 1
configuration:

Absolute hi or lo, de-energized in alarm
Latching output on Form C (AA) Relay

All alarms active on sensor break and
power fail

Alarm setpoint:

Adjustment protection via password

Configuration
security

FM option prevents reconfiguration of alarm
config