3 example: to set up instrument address, 4 data encoding, Example: to set up instrument address – Super Systems 3L Series User Manual

Page 42: Data encoding

Advertising
background image

Operations Manual

Series 3L

42

11.3 Example: To Set Up Instrument
Address

This can be done in operator level 3:-

Do This

Display View

Additional Notes

1.

Press

as

many times as
necessary to
select ‘COMMS
LIST’

Scrolling display
‘c o m m s l i s t ’

2.

Press

to

scroll to ‘ID

3.

Press

or

to select

EIA

485 comms

Scrolling display
‘i d ’

4.

Press

to

scroll to
‘ADDR’

5.

Press

or

to select

the address for
the particular
indicator

Up to 254 can be
chosen but note
that no more than
33 instruments
should be
connected to a
single

EIA

485 link.

Scrolling display
‘a d d r e s s ’

11.4 DATA ENCODING

Modbus data is normally encoded into a 16 bit signed
integer representation.

Integer format data, including any value without a
decimal point or represented by a textual value (for
example ‘off’, or ‘on’), is sent as a simple integer value.

For floating point data, the value is represented as a
‘scaled integer’, in which the value is sent as an integer
which gives the result of the value multiplied by 10 to
the power of the decimal resolution for that value. This
is easiest to understand by reference to examples:

FP Value

Integer Representation

FP Value

Integer Representation

9.

9

-1.0

10

123.5

1235

9.99

999

It may be necessary for the Modbus master to insert or
remove a decimal point when using these values.

Advertising