Series 3L Indicators

31

8. Digital Inputs

The Series 3L comes with two digital inputs, LA and LB.

8.1 Digital Input Parameters

The input is typically from a voltage free contact, which can be configured to operate a number of functions as
determined by parameters in the LA and LB Lists:-

LOGIC INPUT LIST ‘LA’ / ‘LB’

Name

Scrolling

Display

Parameter Description

Value

Default

Access

Level

L.TYPE

LOGIC INPUT
TYPE

Input channel type

L.IP

Logic input

As order
code

Conf
Read only

L.D.I N

LOGIC INPUT
FUNCTION

To configure the function
of the digital input

none Input not used

Ac.AL

Conf

Ac.AL Alarm acknowledge
aL.in Alarm inhibit. See note 1
p.rst Peak value reset
free Freezes the current displayed

value

Loc.b Keylock
rec

Recipe select

UP

Remote key ‘Up’

dwn

Remote key ‘Down’

L.SENS

LOGIC INPUT
SENSE

To configure the polarity of
the input channel

nor

Normal

nor

Conf

Inv

Inverted

Note 1:

This input may be used, for example, in part of an automated process where it is required to prevent alarms from being
displayed during a particular part of the process. It should be used with care – blocking alarms or delayed alarms may
be an alternative.