9.3.1 Example: To Configure Alarm 1

Enter configuration level as described. Then:-

Do This

The Display You

Should See

Additional Notes

1.

Press

as many times as

necessary to select ‘ALARM’

2.

Press

to select ‘A1.TYP’

3.

Press

or

to select the

required alarm type

Alarm Type choices are:-
none Alarm not configured
Hi Full Scale High
Lo Full Scale Low
r.roc Rate of change rising
F.roc Rate of change falling

4.

Press

to select ‘A1.- - - ‘

5.

Press

or

to set the alarm

trip level

This is the alarm threshold setting for Alarm 1.
Characters (- - - ) shown after the alarm number
indicate the type of alarm configured from the above
list.

The alarm threshold is shown in the upper display.

In this example the high alarm will be detected when
the measured value exceeds 215

6.

Press

to select ‘A1 STS’

This is a read only parameter which shows the status
of the alarm output

7.

Press

to select ‘A1 HYS’

8.

Press

or

to set the

hysteresis

In this example the alarm will cancel when the
measured value decreases 2 units below the trip level
(e.g. at 213 units in this example)

9.

Press

to select ‘A1 LAT’

10. Press

or

to select the

latching type

Latching Type choices are:-
none No latching
Auto Automatic
Man Manual
Evt Event
See section 9.1 for an explanation of latching alarms

11. Press

to select ‘A1 BLK’

12. Press

or

to ‘

Yes’ or ‘No’

13. Repeat the above to configure alarms

2, 3 and 4 if required

14. Continue to press

to set up a

delay before the alarm is indicated