7. Input/Output Channels

Indicators are ordered with two form A relays and one form C relay. These form A relays can be configured for a variety
of process applications and the form C relay is typically an FM approved high limit alarm output.

7.1 Output Channel 1 (OP-1) – Series 3L Indicators

Output 1 is always a form A relay in the indicator and is connected to terminals 1A and 1B. It is typically used to
provide external indication of alarms. OP1 beacon is operated from this output.

Output 1 is configured using the parameters in the following table:-

OUTPUT LIST 1 ‘o p -1 ’

Name

Scrolling Display

Parameter

Description

Value

Default

Access

Level

1.I D

I/O 1 TYPE

Displays the type of
output

ReLy Relay output

ReLy

Read
only

1.FUNC

I/O 1 FUNCTION

The function may be
turned off, otherwise
set to

d.out

none

Disabled. If disabled no further
parameters are shown

none

Conf

d.out Digital output

1.SRC.A

I/O 1 SOURCE A

Selects the source of
an event which will
operate the output
relay

The output status is
the result of an OR of
Src A, Src B, Src C,
and Src D

Up to four events can,
therefore, operate the
output
See section 7.1.2.

none No event connected to the

output

none

Conf

1.SRC.B

I/O 1 SOURCE B

1.--- Alarm 1

The --- indicates the
alarm type. If the
alarm is not
configured
AL.(Alarm no) is
shown

2.--- Alarm 2

1.SRC.C

I/O 1 SOURCE C

3.--- Alarm 3
4.--- Alarm4

1.SRC.D

I/O 1 SOURCE D

ALL.A All alarms. Logical AND of

alarms 1 to 4.

nw.AL Any new alarm
Pwr.f Power fail. See also section

7.1.3.

O.rng Output relay operates if the

indicator input is over range

sbr

Sensor break alarm

1.SENS

I/O 1 SENSE

To configure the
sense of the output
channel.
See also section 7.1.1

nor
Inv

Normal
Inverted

nor

Conf