6.1.3 PV Offset

All ranges of the indicator have been calibrated against
traceable reference standards. This means that if the
input type is changed it is not necessary to calibrate the
indicator. There may be occasions, however, when you
wish to apply an offset to the standard calibration to
take account of known errors within the process, for
example, a known sensor error or a known error due to
the positioning of the sensor. In these instances it is
not advisable to change the reference (factory)
calibration, but to apply a user defined offset.

PV Offset applies a single offset to the temperature or
process value over the full display range of the indicator
and can be adjusted in Level 3. It has the effect of
moving the curve up a down about a central point as
shown in the example below:-

6.1.3.1 Example: To Apply an Offset:-

Connect the input of the indicator to the source device
which you wish to calibrate to

Set the source to the desired calibration value

The indicator will display the current measurement of
the value

If the display is correct, the indicator is correctly
calibrated and no further action is necessary. If you
wish to offset the reading:-

Do This

Display

Additional Notes

1.

Select Level

3 or Conf as
described in
Chapter 2. Then

press

to

select ‘INPUT’

Scrolling display
‘p r o c e s s
i n p u t l i s t ’

2.

Press

to

scroll to ‘PV/OFS’

3.

Press

or

to adjust the

offset to the
reading you
require

Scrolling display
‘p v o f f s e t ’

In this case an
offset of 2.0 units
is applied

It is also possible to apply a five point offset which
adjusts both low and high points. This is done in Level
3 using the CAL List, and the procedure is described in
the Calibration section 1212.2.1.

6.1.4 PV Input Scaling

Input scaling applies to the linear mV and volts input
ranges only. This is set by configuring the INPUT
TYPE parameter to

mV or VoLt, mV has an input range

of –10 to 80mV. Using an external burden resistor of
2.49

Ω, the indicator can be made to accept 4-20mA

from a current source. Scaling of the input will match
the displayed reading to the electrical input levels from
the transducer. PV input scaling can only be adjusted
in Configuration level and is not provided for direct
thermocouple or RTD inputs.

The graph below shows an example of input scaling,
where it is required to display 2.0 when the input is 4mV
and 500.0 when the input is 20mV .

If the input exceeds +5% of the

inp.Lo or inp.Hi

settings, sensor break will be displayed.

6.1.4.1 Example: To Scale a Linear Input

Select Configuration level as described in Chapter 2.
Then:-

Do This

Display

Additional

Notes

1.

Then press

to select ‘i n p u t ’

Scrolling display
‘p r o c e s s
i n p u t l i s t ’

2.

Press

to

scroll to ‘i n . t y p ’

3.

Press

or

to ‘

mV’or VoLt

Scrolling display
‘i n p u t t y p e ’

4.

Press

to

scroll to ‘i n p . h i ’

5.

Press

or

to ’

20.00’

Scrolling display
‘l i n e a r i n p u t
h i g h ’

6.

Press

to

scroll to ‘i n p . l o ’

7.

Press

or

to ‘

4.00’

Scrolling display
‘l i n e a r i n p u t
l o w ’

8.

Press

to

scroll to ‘r n g . h i ’

9.

Press

or

to ‘

500.0’

In operator level
the indicator will
read 500.0 for a
mV input of
20.00

10. Press

to

scroll to ‘r n g . l o ’

11. Press

or

to ‘

2.0’

In operator level
the indicator will
read 2.0 for a
mV input of 4.00

i n p u t

2.0

pv.ofs

mv

i n . t y p

500.0

r h g . h i

2.0

r h g . l o

For mA inputs
4-20mA = 9.96-49.8mV with
2.49

Ω load resistor

0-20mA = 0-49.8mV with
2.49

Ω load resistor

mA input will detect sensor
break if mA < 3mA
Use a current source to
remove shunt resistor errors

i n p . l o eg
4 mV

Electrical Input

Display
Reading

R N G . H I
eg 500.0

R n g . l o
eg 2.0

i n p . h i
eg 20 mV

Electrical Input

Display
Reading

Fixed offset

(e.g. 2)

Factory
calibration