1 sense, 2 source, 3 power fail – Super Systems 3L Series User Manual

Page 27: Sense, Source, Power fail, Rely 1.i d, D.out 1 . f u n c

Advertising
background image

Series 3L Indicators

27

7.1.1 Sense

For an alarm output set this parameter to ‘

Inv’ so that

it de-energizes to the alarm state.

7.1.2 Source

The four parameters SOURCE A, SOURCE B,
SOURCE C, and SOURCE D appear when the output
is configured as a digital output i.e. ‘-.FUNC’ = ‘

d.Out’

and provide the facility to connect up to four alarms to
operate a single relay output. If any one of the events
becomes true then the output relay will operate.

7.1.3 Power Fail

An output, configured as a digital output, can be made
to operate following a power fail. It can be
acknowledged in the same manner as an alarm but no
alarm message is given.

7.1.4 Example: To Configure OP-1 Relay to
Operate on Alarms 1 and 2:-

Do This

Display

Additional

Notes

1.

From any

display, press

as many times as
necessary to select
‘O p -1’

Scrolling display
‘o P - 1 l i s t ’

2.

Press

to

scroll to ‘1. i d

This is the
identification of
the hardware
fitted and cannot
be adjusted.

3.

Press

to

scroll to
‘1. F U N C ’

4.

Press

or

to select

d.out’

The output is
configured as a
digital output
function.

Scrolling display
‘o p 1
f u n c t i o n ’

5.

Press

to

scroll to ‘1. S R C . A ’

6.

Press

or

to select the

event which you
want to operate the
output

The output will
activate if either
alarm 1 is
triggered.

Note:-

1.

indicates the
alarm number,
Hi indicates the
alarm type.

Scrolling display
‘o u t p u t 1
s o u r c e a ’

7.

If a second

event is required to
operate the same

output, press

to

select ‘1. S R C . B ’

8.

Press

or

to select the

second event which
you want to operate
the output, eg ‘

AL.2’

Scrolling display
‘o u t p u t 1
s o u r c e b ’

Note:- ‘

2’.

indicates the
alarm number,
AL is displayed
if the alarm type
is not
configured.

Continue to
select up to four
events if
required using
1.S R C . C and
1 . S R C . D

9.

Press

S

to

scroll to ‘1. s e n s ’

10. Press

or

to select ‘

Inv’

‘Inverted’ means
a relay output is
energized for
0% PID demand

‘Normal’ means
a relay output is
energized for
100% PID
demand

Scrolling display
‘i o 1 s e n s e ’

reLy

1.i d

d.out

1 . f u n c

SRC.A
SRC.B
SRC.C
SRC.D

SEnS

Output

Nor

Inv

Each source
(SRC) may be
chosen from:-

Alarm 1
Alarm 2
Alarm 3
Alarm 4
All alarms
Any new alarm
Power Fail

OR