Honeywell HERCULINE 2000 User Manual

Page 117

Advertising
background image

Troubleshooting

Troubleshooting Procedures

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

109

7/08

Test Power Distribution PWA

Replace CPU
assembly.

Is correct

voltage present

at test points?

See below.

Remove top

cover of actuator.

Are fuses good?

Replace fuses with
same type and
rating

Yes

D

Check Fuses F1
and F2 on the
power distribution

PWA.

No

Yes

No

Replace Power
Distribution PWA.

Figure 44 Test Power Distribution PWA

Power Distribution PWA Test Points

Connector

Test Points - Pins

Voltage

J2

Pin 1 to pin 7

5 V

J3

Pins 1,2 to pins 3, 4, 8

Pins 3, 4 to pin 7

5 V

9 V

J1

Pins 5, 6 to pins 7, 8

Pins 1, 2 to pins 7, 8

24 V

28 V + or – 3V