Set Up and Calibration Procedures

Input Set Up Group

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

39

7/08

Input Set Up Group

Table 10 lists the parameters and selections available when the SET INPUT group is selected.

On the keypad and local display:

• Press the SET UP key to enter the Input Set Up group.

• Press the FUNCTION key to scroll through the prompts listed in the set up group.

• Press the

or

keys to view selections or change range settings.

Table 10 Input Set Up Group Parameters

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink Prompt

IN TYP

Note: I

f input

type from model

selection guide

is:

0/4-20mA, 0/1-
5Vdc, 0-10Vdc






4-20
0-20

1-5V
0-5V

0-10

R_SP

INPUT ACTUATION TYPE

— This selection specifies the

signal type and range you are going to use for the actuator
input. Be sure that the values configured for the high and low
range, alarm setpoint, etc. are within the measuring range
for the selected signal range.

4 to 20 mA
0 to 20 mA
1 to 5 Volts dc
0 to 5 Volts dc
0 to 10 Volts dc

Remote Setpoint

(via communications)

NOTE: Changing the Input Actuation Type will restore the
actuator calibration to its factory values.

IN TYP

S_90

Series 90 –

0 to 135 ohms.

Note: If input type from model selection guide is: Series 90
control

INP HI

10.0 to 100

default = 100

INPUT HIGH RANGE VALUE

in % is displayed.

NOTE: When Input Type (R_SP or S_90) is selected, Input
Hi is not configurable.

INP LO

0.0 to 90.0

default = 0.0

INPUT LOW RANGE VALUE

in % is displayed.

NOTE: When Input Type (R_SP or S_90) is selected, Input
Hi is not configurable.