Set Up and Calibration Procedures
Relays Set Up Group

48

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Relay Type – Upper Limit Travel with Hysteresis

Selecting relay type ULim will cause the relay to energize when the motor position exceeds the upper limit
trip point, and can be set up as follows. Note that relay hysteresis parameter (RLY1HY) value is set to 10,
which is 10% of range. This means that when the relay is energized, due to the motor position exceeding
the upper limit value, the relay will not de-energize until the motor moves to 10% below the trip point.

Set Up Group

Parameter

Value

SET RELAY2

RTYP21

ULim

R21VAL

70.0

R21HL

HI

RTYP22

NONE

RLY2HY

10.0

100%

0%

Closed

70%

RELAY n

Normally Open

Motor
Position

60%

100%

0%

Closed

70%

RELAY n

Normally Open

Open

Motor
Position

60%H

y
s
t
e
r
e
s
I
s

H
y
s
t
e
r
e
s
I
s

Open

Relay Type – Motor Starts

Selecting relay type STRT will cause the relay to trip when the number of motor starts exceeds the selected
limit. The motor starts value is stored as one of the maintenance group statistics. This example sets the
motor starts limit at 200,000 for Relay 1.

Set Up Group

Parameter

Value

SET RELAY1

RTYP11

STRT

R11

E*

X10K

R11VAL

20

R11HL

HI

RTYP12

NONE

The resulting action is that Relay 1 will trip when the number of accumulated motor starts in the
maintenance group exceeds 200,000.