Set Up and Calibration Procedures

Calibration

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

69

7/08

Table 25 Input Calibration Procedure

Step

Operation

Press

Result

1

Enter Calibration
Mode

SETUP

until you see

Upper Display

=

CAL

Lower Display

=

INPUT

FUNCTION

Upper Display

=

DIS

Lower Display

=

CAL IN

or

key

Upper Display

=

BEGN

Lower Display

=

CAL IN

2

Calibrate Zero (0%)

FUNCTION

Upper Display

=

APLY

Lower Display

=

INZERO

Adjust the signal source to an output value equal to 0% range
value.

Wait 5 seconds, then go to step 3.

3

Calibrate Span
(100%)

FUNCTION

Upper Display

=

APLY

Lower Display

=

INSPAN

Adjust the signal source to an output value equal to 100%
range value.

Wait 5 seconds, then go to step 4.

4

FUNCTION

Calibration for zero and span input values are now saved. Input
calibration is complete.

NOTE: The display will automatically go to the CAL MOTOR set
up display. See Table 26. You may also exit calibation mode by
pressing the DISPLAY or SETUP keys.

ATTENTION:
When calibrating the motor to a short stroke range, you must
reset the end-of-travel limit switches. See Setting End-of-Travel
Limit Switches.