Set Up and Calibration Procedures
Regions of Motor Travel

62

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Regions of Motor Travel

The full span of motor travel can be 90

° or 150° rotation. The span is divided into 10 regions of motor

travel as shown in Figure 23 (regions are numbered 0 through 9). Maintenance statistics are accumulated
on the total number of motor starts, as well as the total number of motor starts that occur in each region of
travel. The statistics can be accessed in the maintenance set up group. The counts can also be reset to zero
if desired. See the Maintenance Set Up Group for more information. The regions of travel are determined
by the full span motor travel (90

° or 150° rotation). If the actuator is set up to operate in a smaller range,

for example between 40% and 80% of full span, the maintenance statistics will show motor starts only in
regions 4 through 7.

Degrees of Rotation

Percent of Span

0o 30o 60o 90o

0% 20% 40% 60% 80% 100%

Region of Travel

0 1 2 3 4 5 6 7 8 9

De gr ee s of R ot at io n

Pe rc en t of S pa n

0o

30 o

60 o

150 o

0%

20%

4 0%

60%

8 0%

100%

Regio n of Trave l

0 1

2 3

4 5 6

7 8

9

Figure 23 Regions of Motor Travel