Set Up and Calibration Procedures
Set Up Groups

34

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Set Up Groups

Pressing the SET UP key on the keypad provides access to the various set up groups and allows you to set
up operating parameters, (such as input types and alarms), calibrate the actuator’s inputs and outputs, set
communications, and check actuator status. Table 8 on the next page lists the set up groups that are
available by using the SET UP and FUNCTION keys on the keypad.

Table 8 Set Up Groups

Set Up Group Title

Pressing the FUNCTION Key Allows You to…

For Details, See

SET

INPUT

Select and set various parameters associated with the
input signal to the actuator.

Table 10

SET

RELAYn

n

= 1, 2, 3, or 4

Select relay functions. NOTE: Set Relay groups will
show on display only if relays are installed in the
actuator.

Table 13

SET

CUROUT

Select the output signal type of the actuator.

Table 15

SET

COMM

Select communication parameters for remote control of
actuator when connected to a SCADA system.

Table 16

SET

DIGINP

Select the parameters for external digital input states.

Table 17

SET

DISPLA

Select and set parameters for the local display.

Table 18

CAL

INPUT

Calibrate input zero and span values.

Calibration
Procedure,

Table 25

CAL

MOTOR

Calibrate zero and span values for motor operation.

ATTENTION

When calibrating the motor to a short stroke range,
you must reset the end-of-travel limit switches. See
Setting End-of-Travel Limit Switches.

Calibration
Procedure,

Table 26

CAL

CURENT

Calibrate actuator output.

Calibration
Procedure,

Table 27

SET

LOCK

Set or change security password. Enable or disable
security access to set up parameters and calibration
set up.

Table 19

READ

STATUS

Display operating and alarm status. Display self-test
diagnostic results.

Table 20

SET

DRVINF

Display and/or set various parameters specific to the
actuator.

Table 21