Split Range

26

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Split Range

The HercuLine

®

2001/2002 actuators can be set up to operate within a narrow input range (for example,

4 to 12mA input) in certain applications. The procedure in Table 5 describes how to set up an actuator
to operate as part of a split valve configuration.

Table 5 Split Range Set Up Procedure

Step

Action

To Set Actuator span to operate from 4 to 12 mA input.

1

Enter Set Up mode by pressing SET UP key

2

Select SET INPUT group

3

Press FUNCTION key until INP HI (on lower display) is selected.

4

Set INP HI value to 50.0

5

Press FUNCTION key to select INP LO and set value to 0.0

6

Press DISPLAY key to exit Set Up mode.

To Set Actuator span to operate from 12 to 20 mA input.

1

Enter Set Up mode by pressing SET UP key

2

Select SET INPUT group

3

Press FUNCTION key until INP HI (on lower display) is selected.

4

Set INP HI value to 100.0

5

Press FUNCTION key to select INP LO and set value to 50.0

6

Press DISPLAY key to exit Set Up mode.

ATTENTION

Be sure to review failsafe strategy for your process application.

Master/Slave Arrangement

Introduction

With the motor positioner, the controlling signal for the actuator is a 4 to 20mA from a current output
controller as shown in the flow diagram in Figure 16.

Unlike the position output controller, the current output controller must produce a continuous analog
signal or the actuator will revert to one of its failsafe states. Signal failure is not a problem since the
available failsafe settings allow you to set the actuator position on signal loss.