Set Up and Calibration Procedures

Lock Set Up Group

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

53

7/08

Lock Set Up Group

Table 19 lists the parameters and selections available for the SET LOCK group.

Table 19 Lock Set Up Group Parameters

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink

®

Prompt

LOCKID

0 to 4095

default = 0

PASSWORD LOCK

4-digit password can be selected to

provide security access to calibration information, set up
parameters and supervisory functions. Password can be a
number from 0 to 4095.

LOCK


NONE


CAL


CONF


FULL

default = NONE

LOCK OUT FEATURE

— Selects lockout security for

calibration and supervisory functions, and set up groups.

None

— No lockout of any calibration or set up groups. You

select and change set up group values, and perform field
calibration.

Calibration

— Lockout for calibration groups SET CALINP,

SET CALMTR, SET CALOUT and CAL POSOUT only. You
can select and change set up group values.

Configuration

— Lockout for calibration groups and set up

group configuration. You can only scroll through and view
set up group values.

Full

— Lockout for calibration and all set up group values.

Only SET LOCK and READ STATUS groups are accessible.

MAENAB


DIS

ENAB

default = ENAB

Manual / Auto

— Allows the ability to lockout mode changes

from the front panel.

Disabled

— Disables the front panel auto / manual switch

functionality.

Enabled

— Enables the front panel auto / manual switch

functionality.