Set Up and Calibration Procedures

Input Set Up Group

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

41

7/08

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink Prompt

FSFTYPL






LAST

UP

DOWN

USER

default = DOWN

FAILSAFELO TYPE

—Selects the motor position you want

the actuator to go to when input signal is below the low end
range value or on loss of input signal.
NOTE: Failsafe condition occurs when the input exceeds its
low end range value by 3%, or when the input signal goes to
zero. For input types 0 to 20mA, 0 to 5 V, and 0 to 10 V
there is no failsafe condition at the zero value.

Last Position

—Actuator motor remains at last position.

Up

—Actuator motor moves to full scale value.

Down

—Actuator motor moves to zero value.

User selected value

—Actuator motor moves to a customer-

defined value.

*

Allows setting of failsafelo input value.

FsFVALL *

0

to 100%


default = 0

FAILSAFELO INPUT VALUE

—(FailsafeLO Type USER

only) Selects the motor position you want the actuator to go
to when input signal is below the low end range value or on
loss of input.
Range is from 0 to 100%.

CHAR

LINR

SQRT

CUST

default = LINR


INPUT CHARACTERIZATION

Selects a characterization

type that causes the actuator to characterize a linear input
signal to represent a non-linear input.

Linear

— Provides linear characterization of the input signal.

Square Root

Provides square root characterizations of

the input signal.

Custom

— Custom characterization. Selecting custom

allows you to create a twentieth order characterization of
input value (x) and associated shaft position (y).
NOTE: Selecting CUST input characterization causes the
following prompt CUSTOM to be displayed.

CUSTOM

EQUL

QUIK

USER

default = EQUL

Equal percentage –

Sets the characterization as explained

in Equal Percentage Valve Characteristic on page 42.
Values are read-only.

Quick opening

- Sets the characterization as explained in

Quick Opening Valve Characteristic on page 43. Values are
read-only.

User-configurable

– Lets you create your own

characterization using the following Xn VAL and Yn VAL
prompts.

Xn VAL

n = 1 - 20

0 to 100 %

Input Value

as a percentage of input range. Defaults are

in increments of 5%.

Yn VAL

n = 1 - 20

0 to 100 %

Shaft Position Value

as a percentage of position range.

Defaults are in increments of 5%.