Set Up and Calibration Procedures
Relays Set Up Group

44

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Relays Set Up Group

ATTENTION

The Relay set up group parameters are accessible only if relay PWAs are installed in the
actuator. HercuLine

®

2001 actuators can be equipped with one PWA –for a total of two SPDT

relays. Using the Relay set up groups you can program the installed relays to operate in
response to various operating conditions.

Table 13 lists the parameters and selections available when the SET RELAYn group is selected.

Table 13 Relay Set Up Group Parameters

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink

®

Prompt

RTYPny

n

= 1, 2, 3, or 4

y

= 1 or 2

NONE

InPR

PosR

DEV

ULim

LLim

T Hi

T Lo

STRT

STAL

MAN

PWRF

FsFA
PosF

DiGI

TDEG

default = InPR and

NONE

RELAY TYPE

— Selects the relay number and the relay

activation type. See Table 14 Relay Type Descriptions.

Input Range

Upper / lower limits of input signal exceeded

Position Range

— Upper / lower limits of motor position

exceeded
Deviation

— Deviation from input exceeded

Upper Limit Travel

— Same as PosR for upper limit

Lower Limit Travel

Same as PosR for lower limit

Temperature High

— High temperature limit exceeded

Temperature Low

Low temperature limit exceeded

Starts

— Motor starts limit exceeded. Allows setting of

multiplier value.
Stalled

Motor position does not follow input

Manual

— Actuator is set to manual mode

Power Up Test Failure

— Failure of any power up diagnostic

Failsafe Alarm

Failsafe condition detected

Position Sensor Signal Failure

position output out of valid

range
Digital Input

— Digital input closure

Total Degrees

total degrees traveled. Allows setting of

multiplier value.

RnyE*

X1

X10k

default = X1

MULTIPLIER

— (Relay Types STRT and TDEG only)

Selects the multiplier for the number limit of motor starts and
total degrees traveled before the relay is activated. Multiplier
specifies the value on display as times one (X1) or times ten
thousand (X10k).

RnyVAL

n

= 1, 2, 3, or 4

y

= 1 or 2

0.0 to 100.0

RELAY VALUE

— Sets numerical value of limit where relay

trips (energizes). Units are determined by the relay type
selection. See Table 14 Relay Type Descriptions for units.

Rny HL

n

= 1, 2, 3, or 4

y

= 1 or 2

HI

LO

RELAY HIGH/LOW

— Sets relay trip point to high or low

limit.

RLYnHY

n

= 1, 2, 3, or 4

0.0 to 100.0

(in percent)

RELAY HYSTERESIS

— 0.0 to 100.0% of span or full output.

NOTE: Relay Hysteresis parameter is accessible only if
appropriate relay type is selected.

n

is the relay number, y is the relay contact.