Table 12 quick opening valve characteristic – Honeywell HERCULINE 2000 User Manual

Page 51

Advertising
background image

Set Up and Calibration Procedures

Input Set Up Group

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

43

7/08

Quick Opening Valve Characteristic

Table 12 contains values that approximate the characteristic of a quick opening control valve. When the
QUIK custom characterization type is selected, the values in Table 12 are automatically loaded into the
actuator configuration to produce the characteristic as presented in the graph. The Xn VAL is the input
value as a percentage of range and Yn VAL is the characterized output (actuator shaft position) as a
percentage of range.

Table 12 Quick Opening Valve Characteristic

Order

Xn VAL

% of

Range

Yn Val

% of

Range

Quick Opening Valve Characteristic

0 0 0

1 5 10

2 10 20

3 15 30

4 20 40

5 25 50

6 30 60

7 35 70

8 40 77

9 45 82

10 50 86

11 55 88

12 60 90

13 65 92

14 70 94

15 75 95

16 80 96

17 85 97.5

18 90 98.5

19 95 99.5

20 100 100

Xn VAL - Actual Input

10 20 30 40 50 60 70 80 90 100

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

Y

n

V

A

L

-

C

h

a

ra

c

te

ri

z

e

d

O

u

tp

u

t

Advertising