Set Up and Calibration Procedures

Digital Input Set Up Group

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

51

7/08

Digital Input Set Up Group

Table 17 lists the parameters and selections availible for the SET DIGINP group.

Table 17 Digital Input Set Up Group Parameters

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink

®

Prompt

DIGINP


NONE

UP

DOWN

USER

default = UP

Digital Input State

Selects the position of the actuator in

response to a digital input signal (contact closure).

None

— No action by the actuator.

Up

— Actuator motor moves to full scale value.

Down

— Actuator motor moves to zero value.

User

selected value— Actuator motor moves to a

customer-selected value.
* Allows setting of End Position Value.

EndPos

0 – 100

(in percent)

END POSITION VALUE

— (DIGINP USER only) Selects the

motor position you want the actuator to go to when digital
input signal present (contact closure).