Set Up and Calibration Procedures
Maintenance Set Up Group

60

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink

®

Prompt

PDA users: The prompts are organized differently on your PDA’s

HercuLink

®

software. Grayed prompts are under Configuration, Maintenance. Non-grayed

prompts are under Maintenance.

DATSAV

DIS

ENAB

MAINTENANCE DATA FORCED SAVE

— Allows you to

manually force a save of the current maintenance data
values.

DISABLE

— Forced data save is disabled.

ENABLE

— Forced data save is enabled.

PASSWRD

nnnn

PASSWORD

If a password has been activated, then a 4-

digit password is required to enable any of the functions
below.

NOTE: Password is set (or changed) from the Lock set up
group.

MANRST


NONE

STAL

STRT

REGNn

n

= 0 to 9

TEMP

TDEG

RELn

n

= 1, 2, 3 or 4

ALL

SYST

default = NONE

MAINTENANCE STATISTIC RESET

Allows reset of the

following maintenance statistics:

None

— No reset of maintenance statisitics

Stall

— Resets accumulated stall time to zero.

Motor Starts

— Resets the accumulated motor start counter

to zero.

Motor Starts in the Region

— Resets the selected motor

span region counter to zero.

Temperature Statistics

— Resets the high / low

temperature limit statistics.

Total Degrees

— Resets the total degrees of motor travel to

zero.

Relay Counts

— Resets the selected accumulated relay

cycle counter to zero.

All

— Resets all maintenance statistics to zero.

SYST

— Enables the system restart function.