Calibration

70

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Calibrate Motor

Use the procedure in Table 26 to calibrate the actuator motor for 0% and 100% input signal

ATTENTION

For a motor calibration to be saved, you must complete the procedure. The calibration will not
be saved if you exit without completing the steps of the procedure.

ATTENTION

When calibrating the motor to a short stroke range, you must reset the end-of-travel limit
switches. See Setting End-of-Travel Limit Switches.

Table 26 Motor Calibration Procedure

Step

Operation

Press

Result

1

Enter Calibration
Mode

SETUP

until you see

Upper Display

=

CAL

Lower Display

=

MOTOR

FUNCTION

Upper Display

=

DIS

Lower Display

=

CALMTR

or

key

Upper Display

=

BEGN

Lower Display

=

CALMTR

2

Calibrate Zero (0%)

FUNCTION

Upper Display

=

APLY

Lower Display

=

MTR LO

Use the Handwheeel or AUTO/MANUAL switch to manually
drive the actuator motor to its low position.

Wait 5 seconds, then go to step 3.

3

Calibrate Span
(100%)

FUNCTION

Upper Display

=

APLY

Lower Display

=

MTR HI

Use the Handwheeel or AUTO/MANUAL switch to manually
drive the actuator motor to its high position.

Wait 5 seconds, then go to step 4.

4

FUNCTION

Calibration for zero and span motor positions are now saved.
Motor calibration is complete.

NOTE: The display will automatically go to the CAL CURENT
set up display. See Table 27. You may also exit calibation
mode by pressing the DISPLAY or SETUP keys.