Installation

Electrical Installation

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

19

7/08

HercuLine

®

2001/2002 with Auto/Manual Terminal Connections

Table 4 Terminal Connections: HercuLine

®

2001/2002 with auto/manual

Connection

Terminal Numbers

and LABEL

See Figure 9

Descriptions

TB1

Hot

1

Hot wire for 120/240VAC mains supply

Neutral

2

Neutral wire for 120/240VAC mains supply

Protective Ground

3

Ground wire connection for mains supply

Auto/Manual Switch
Contact

4
5

Switch contact to indicate setting of actuator AUTO/MANUAL
switch.
Switch is closed when actuator is “NOT-IN-AUTO”

6

TB3

4 to 20mA Output*

1 (+)
2 (-)

Analog signal output

Feedback 3

Feedback signal used in conjunction with 4 to 20mA OUTPUT
voltage when using Slidewire Emulation

4 to 20mA Input

4 (+)
5 (-)

Analog signal input

Modbus
Communication

6 (+)
7 (-)
8 Shield

Connection for RS485 Modbus loop wires

HART Communications

4 (+)
5 (-)

HART Communication is 4-20 mA only.

Digital Input

9 Com
10 Input

Customer’s contact closure

Auxiliary

Connector

_

Brown

Black

Blue

+

Black Wire Not Used

HART connection using
external Turck connector

+

_

HART

Communications

Connection

Auxiliary

Connector

_

Brown

Black

Blue

+

Black Wire Not Used

HART connection using
external Turck connector

Auxiliary

Connector

_

Brown

Black

Blue

+

Black Wire Not Used

HART connection using
external Turck connector

+

_

HART

Communications

Connection

Figure 9 HercuLine

®

2001/2002 connections