Set Up and Calibration Procedures

Relays Set Up Group

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

47

7/08

Relay Type - Deviation

Setting up a relay to alarm (energize) when the motor position deviates 10% (+ or -) from the actuator
setpoint can be set up as follows.

Set Up Group

Parameter

Value

SET RELAY1

RTYP11

DEV

R11VAL

10.00

R11HL

HI

RTYP12

DEV

R12VAL

-10.00

R12HL

LO

RLY1HY

0.0

The resulting action is shown below.

100%

0%

Closed

-10%

RELAY n

Normally Open

Closed

Open

Motor
Position

Input

50%

+10%