Preferred wiring, Alternate wiring – Honeywell HERCULINE 2000 User Manual

Page 38

Advertising
background image

Burner Control/Flame Safety
Master/Slave Arrangement

30

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Split Valve Configuration

A common heat or cool type process requires two valves. In this case the controller has only one output.
The two motor positioners are calibrated differently, one responds to 4 to 12mA and the other responds
to 12 to 20mA. At 12mA, both valves are closed; one opening below 12mA and the other above 12mA.
Refer to Figure 20 for an interconnection diagram for split valve operation using two actuators.

Hot

10260S Series Actuator #1

Neutral

Ground

120/240

VAC

250 Ohms
1 to 5 VDC

+

-

Current Output Controller

4 to 20 mA

Hot

10260S Series Actuator #2

Neutral

Ground

120/240

VAC

250 Ohms
1 to 5 VDC

Preferred
Wiring

Note: Controller must
be capable of sourcing
the impedance.

NOTE: If using HART

®

communications, for this application HART

®

must be configured for Multi-drop operation.

Hot

10260S Series Actuator #1

Neutral

Ground

120/240

VAC

250 Ohms
1 to 5 VDC

+

-

Current Output Controller

4 to 20 mA

Hot

10260S Series Actuator #2

Neutral

Ground

120/240

VAC

Alternate
Wiring

Figure 20 Interconnection Diagrams

NOTE: If using HART

®

communications, for this application HART

®

must be configured for Multi-drop operation.

Actuator #1

Actuator #2

Actuator #1

Actuator #2

Jumper W2
= Current

Jumper W2
= Current

Jumper W2
= Current

Jumper W2
= Voltage

See Figure
27 for jumper
location

See Figure
27 for jumper
location