Table 11 equal percentage valve characteristics – Honeywell HERCULINE 2000 User Manual

Page 50

Advertising
background image

Set Up and Calibration Procedures
Input Set Up Group

42

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Equal Percentage Valve Characteristic

Table 11 contains values that approximate an equal percentage valve characteristic in the actuator. When
the EQUL custom characterization type is selected, the values in Table 11 are automatically loaded into the
actuator configuration to produce the characteristic as presented in the graph. The Xn VAL is the input
value as a percentage of range and Yn VAL is the characterized output (actuator shaft position) as a
percentage of range.

Table 11 Equal Percentage Valve Characteristics

Order

Xn VAL

% of

Range

Yn Val

% of

Range

Equal Percentage Valve Characterization

0 0 0

1 5 0.8

2 10 2.1

3 15 3.2

4 20 4.9

5 25 6.5

6 30 8.4

7 35

10.7

8 40

13.2

9 45

15.7

10 50 18.7

11 55 22.6

12 60 27.2

13 65 33.4

14 70 40

15 75 46

16 80 53.8

17 85 63.2

18 90 73.7

19 95 86.2

20 100 100

10 20 30 40 50 60 70 80 90 100

Xn VAL - Actual Input

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

Y

n

V

A

L

-

C

h

a

ra

c

te

ri

z

e

d

O

u

tp

u

t

Advertising