Set Up and Calibration Procedures

CAL POSOUT Group

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

63

7/08

CAL POSOUT Group

The CAL POSOUT group is used to verify that the position sensor is operating and adjusted properly. This
group allows the local display to indicate the output voltage of the position sensor. This display is used
when verifying the POS sensor is operating and that it is properly calibrated. Table 23 shows the selections
available for the CAL POSOUT group.

Table 23 CAL POSOUT Group Parameters

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink Prompt

CALPOS

n.nnn

POSITION SENSOR OUTPUT

Read Only. Displays the

output voltage of the position sensor

To access the display…

Press

Result

SETUP

until you see

Upper Display

=

CAL

Lower Display

=

POSOUT

FUNCTION

Upper Display

=

DIS

Lower Display

=

CALPOS

or

key

Upper Display

=

BEGN

Lower Display

=

CALPOS

FUNCTION

Upper Display

=

n.nnn

(sensor output in volts)

Lower Display

=

POSOUT