Table 3 terminal connections: herculine – Honeywell HERCULINE 2000 User Manual

Page 26

Advertising
background image

Installation
Electrical Installation

18

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

HercuLine

®

2000 Terminal Connections

Table 3 Terminal Connections: HercuLine

®

2000

Connection

Terminal Numbers

and LABEL

See Figure 8

Descriptions

Hot 1

Hot wire for 120/240VAC mains supply. Use only if Auto/Manual
switch is present.

Neutral

2

Neutral wire for 120/240VAC mains supply

Auto/Manual Switch
Contact

3
4

Switch contact to indicate setting of actuator AUTO/MANUAL
switch.

Switch is closed when actuator is “NOT-IN-AUTO”

CW from Controller

5

CW motor drive

CCW from Controller

6

CCW motor drive

Potentiometer #1

7
8
9

Clockwise-End
Slider
Counterclockwise-End

Potentiometer #2

10
11
12

Clockwise-End
Slider
Counterclockwise-End

Protective Ground

Ground wire connection for mains supply

158 ohm

158 ohm

Install resistors to convert 1000 ohm
potentiometer to 135 ohms

1

1

REQUIRED ONLY IF AUTO/MANUAL
SWITCH IS PRESENT

158 ohm

158 ohm

Install resistors to convert 1000 ohm
potentiometer to 135 ohms

1

1

1

1

REQUIRED ONLY IF AUTO/MANUAL
SWITCH IS PRESENT

Figure 8 HercuLine

®

2000 connections